• No products in the cart.

10K-M

$1,230.60 Add to Cart

The 10K-M is a robust, durable leak detection controller with a small footprint and a unique enclosure that allows it to be mounted on a DIN rail.  The 10K-M does not have a web interface.

The 10K-M Features:

  • Distance-read leak detection.
  • Monitors up to 10,000 feet (3,048 meters) of RLE’s chemical sensing cable.
  • Compatible with SeaHawk chemical sensing cable.
  • Includes the leader cable and EOL that are compatible with chemical sensing cable.
  • Audible and visible alarm notification.
  • Panel and DIN rail mountable enclosure.
  • Can be networked with other RLE web-accessible controllers or any other Modbus RTU-equipped monitoring system.

Make Sure You Have An Isolated Power Supply!

RLE leak detection controllers, including the 10K-M, require an isolated power supply. A power supply is not included with the 10K-M. Purchase an RLE power supply – PSWA-DC-24-ST or WA-AC-24-ST.

Click here for more information about RLE leak detection controllers and isolated power supplies.

Included Equipment: SeaHawk 10K controller, chemical cable leader cable, end-of-line (EOL) terminator

Additional Requirements: Isolated RLE power supply, sensing cable (as needed for application)

Power: Requires an isolated power supply.

  • 12-24VDC (±10%) Isolated, 50-60Hz; requires RLE power supply PSWA-DC-24-ST (not included)
  • 12-24VAC (±10%) Isolated, 50-60Hz; requires RLE power supply WA-AC-24-ST (not included)
  • 400mA max @ 12VAC/DC; 200mA max @ 24 VAC/DC

Output Relay: 1 Form C, 5A resistive @ 30VDC, 8A resistive @ 250VAC, Minimum load 10mA @ 5VDC (Signal)

Inputs

  • Leak Detection Cable: Compatible with all SeaHawk chemical sensing cables (not included)
  • Cable Input: Requires 15ft (4.6m) leader cable and EOL terminator (included)
  • Maximum Length: 10,000ft (3048m) of chemical sensing cable
  • Minimum Length: 35ft (11m)
  • Detection Accuracy: ± 2ft (0.6m) +/- 0.5% of the cable length
  • Detection Repeatability: ± 2ft (0.6m) +/- 0.25% of the cable length
  • Detection Response: When used with sensing cable, 5-990sec. (selectable).

Communication Ports

  • EIA-485: 1200, 9600, or 38400 baud, N2 (selectable); Parity: none, 8 data bits, 1 stop bit

Protocols

  • EIA-485: Modbus RTU Server; N2

Alarm Notification

  • Visible Alarm: Red LED for leak alarm; yellow LED for cable contamination or fault; 4-character LED displays distance or fault status
  • Audible Alarm: 85dBA @ 2ft (0.6m); re-sound configurable, 0-999min.

Front Panel Interface

  • 4-character LED: Displays leak or contamination distance or fault status.
  • 6 LED Indicators:
    • Red: Leak
    • Yellow: Cable Fault or Contamination
    • Green: Power On
    • Green: Measurements made in feet
    • Green: Measurements made in meters
    • Green: Microamps of current on cable
  • Push Button: Test/Reset/Alarm Silence, cycle through device functions

Operating Environment

  • Temperature: 32° to 122°F (0° to 50°C)
  • Humidity: 5% to 95% RH, non-condensing
  • Altitude: 15,000ft (4,572m) max.

Storage Environment: -4° to 158°F (-20° to 70°C)

Dimensions: 2.8”W x 4.3”H x 2.4”D (71mmW x 109mmH x 61mmD)

Weight: 5.3oz. (153g)

Mounting: DIN rail or panel mountable

Certifications: CE; ETL listed: conforms to EN 61010-1; UL 61010-1, certified to CSA C22.2 NO. 61010-1; RoHS compliant

You may also like…

$1,230.60 Add to Cart

[]